Configuration and Use Manual
MMI-20016855
10.25.29 A108
Alert
Basic Event 1 On
Cause
The process has triggered Basic Event 1.
Recommended actions
1. No action is required.
2. Review event configuration if you believe the event was triggered erroneously.
10.25.30 A109
Alert
Basic Event 2 On
Cause
The process has triggered Basic Event 2.
Recommended actions
1. No action is required.
2. Review event configuration if you believe the event was triggered erroneously.
10.25.31 A110
Alert
Frequency Output Saturated
Cause
The calculated Frequency Output is outside the configured range.
Recommended actions
1. Check the Frequency Output scaling.
2. Check process conditions.
Actual conditions may be outside the normal conditions for which the output is configured.
3. Check for air in the flow tubes, tubes not filled, foreign material in the tubes, coating in the tubes, or
other process problems.
4. Verify that the measurement units are configured correctly for your application.
5. Purge the sensor tubes.
Configuration and Use Manual
Troubleshooting
June 2019
165