Section 2: Installation Wiring; Main Supply Circuit; 1: Flps-7 Main Supply Installation Wiring Diagram; 2: Flps-7 Installation Wiring Terminals - Honeywell Gamewell FCI S3 Series Manual

Small addressable fire alarm control panel
Table of Contents

Advertisement

This product is intended to be installed in accordance with local, regional and National standards. The S3
Series System (Small Addressable Fire Alarm Control Panel) comprises the following modules.
SLP-E3 (Smart Loop Panel-Main Board)
SLC-PM or SLC95-PM (Signaling Loop Circuit
Driver
Module for System Sensor or Apollo Loop
Devices)
LCD-SLP
(Lead Crystal Display-Smart Loop Panel)
FLPS-7 (7 Amp Power Supply)

2.1 Main Supply Circuit

The FLPS-7 is the main supply circuit for the S3 Series System.
2.1.1 FLPS-7 Main Supply Installation Wiring Diagram
Figure 2.1.1.1 illustrates the FLPS-7 main supply circuit board diagram.
2.1.2 FLPS-7 Installation Wiring Terminals
Table 2.1.2.1 lists the FLPS-7 power supply installation wiring terminals.
Designation
L1
EARTH
L2
2.1.3 FLPS-7 Main Supply Circuit Specifications
The FLPS-7 is the main supply circuit for the S3 Series panel. Table 2.1.3.1 lists the FLPS-7 specifications.
Circuit Supervision:
Nominal Voltage, Frequency:
Max.current or power supply to be used:
Terminal for the connection of a grounded conductor: See Figure 2.1.1.1.
Operating Temperature:
Operating Humidity:
The maximum time during which the standby
operating source maintains the minimum operating
voltage (85 percent of rated voltage). This is required
for releasing devices under continuous load that can't
maintain 85 percent of the rated operating voltage to
the releasing devices for 60 seconds after energizing.
Type of device (automatic, manual, waterflow,
sprinkler supervisory, watchman supervisory, etc.).
2.1.4 Cabinet Enclosures for the FLPS-7
Table 2.1.4.1 lists the cabinet enclosure you can use to install the SLP main board.
SLP-BB cabinet (also called the B-Slim cabinet)
S3 Series, Cabinet B-Size
10

Section 2: Installation Wiring

Required Modules
J 1
Figure 2.1.1.1 FLPS-7 Main Supply Circuit Board
Description
AC Power - Hot
Earth Ground
AC Power - Neutral
Table 2.1.2.1 FLPS-7 Installation Wiring Terminals
Requirements
Table 2.1.3.1 FLPS-7 Main Supply Circuit Specifications
Cabinet
Table 2.1.4.1 FLPS-7 Main Board Cabinet
S3 Series UL Listing Document — P/N LS10005-051GF-E:D3 3/09/2016
Optional Modules
LCD-E3, LCD-7100/RAN-7100
(Remote Display Modules)
DACT-E3
(Digital Alarm Communicator Transmitter)
ASM-16/ANU-48 (Switch LED Modules)
RPT-E3-UTP (Repeater Module)
– FML-E3 (Fiber-Optic Multi-Mode)
– FSL-E3 (Fiber-Optic Single-Mode)
F L P S -7
J P 6
J P 5
Designation
J1
JP5
JP6
FLPS-7 Specifications
Supervised
120 V AC, 60 Hz, Max. 2.75 Amps
240 V AC, 50/60 Hz, Max. 1.4 Amps
FLPS-7, 7 amperes power supply, 7 A 24 VDC
32° to 120° F (0° to 49° C)
0 to 93%, non-condensing at 90° F (30° C)
N/A
Refer to Section 1.3 (Product Models Nomenclature),
Table 1.3.1 (Product Models Nomenclature).
Part Numbers
SLP-BB
14.1/2" W x 20 1/8" H x 4 1/2" D
S3BB-BB/RB
19.38" W x 19.38" H x 4.50" D
Description
Power output connector
Factory set to 120 VAC
Factory set to 120 VAC
Dimensions

Hide quick links:

Advertisement

Table of Contents
loading