10.7.1 Single Interlock Zone Releasing

A single interlock zone utilizes a minimum of two addressable detectors and a designated
manual release switch.
Only addressable detectors can be used. No conventional detectors can be used.
Each Single Interlock Zone input requires at least one manual release switch.
Conditions Required for an Pre-Alert Output Activation
If any single addressable detector is activated, the "Pre-Alert" output will activate. This alerts
the user that the initial stages required for a release condition are present. (Also refer to Table
10-3.)
Conditions required for an General Alarm and Release Output Activation
If two or more addressable detectors, or a manual release switch activate, the "Alarm" and the
"Release" outputs will activate. (Also refer to Table 10-3).
Inputs
1st Addressable Detector
2nd Addressable Detector
Manual Release Station
10-16
Important!
Table 10-3 Single Interlock Zone Operation