Table 10: Calculation the current consumption
In order to calculate the input current, the currents of the power unit, control and
other loads must be added together. The actual current required can be used for
the consumers. The maximum current must not be exceeded.
Name
Terminals
Voltage
Current consumption
Connection of the external supply
NOTICE! The power-off function is not available if the controller is supplied
externally.
Name
Terminals
Output current
Output voltage
Connection of the control | 4
Brake
Encoder
Digital output DO1
Digital output DO2
Voltage output 24Vout
Sum DO safety module
P24Vin, 0V
X2A.28 (P24Vin)
X2A.27 (0V)
DC 24 V (±5 %)
Calculated value up to max. 4.6 A
28
X2A
27
-
+
24Vout
0V (reference potential)
X2A.16, X2A.26 (24Vout)
X2A.27 (0V)
max. 100 mA (short-circuit proof)
total for both terminals
minimum P24Vin – 3V
maximum P24Vin
Current consumption
0.6 A
0,8 A
Max. 2.0 A
Max. 0.5 A
Max. 0.1 A
Max. 0.1 A
Max. 0.1 A
Max. 0.4 A