Table of Contents Table of Contents Introduction ..............................Markings..............................1.1.1 Warnings..........................1.1.2 Information notes ........................1.1.3 Symbols and markers ......................Laws and guidelines..........................Warranty and liability..........................Support..............................Copyright............................... Validity of this manual ........................... General Safety Instructions.......................... Installation ............................. Start-up and operation .......................... Maintenance............................
Page 4
Table of Contents KEB Automation KG Diagnosis/visualisation X4A ........................Assignment of the terminal strip X4A ....................Data cable RS232 PC-Drive Controller....................USB-serial converter ..........................Connection of the RS485 interface ....................... Fieldbus interfaces............................Type code fieldbus ..........................CAN............................... Ethernet fieldbus interface ........................
Page 5
List of Figures List of Figures Abb. 1 Pin assignment socket D-Sub-9 (top view) .................... Abb. 2 Serial cable for the connection to a PC....................Abb. 3 Connection CAN bus..........................Abb. 4 RJ45 socket front view ........................... Abb. 5 RJ45 socket front view ........................... Abb.
Page 6
List of Tables KEB Automation KG List of Tables Tab. 1 Connector sets ............................Tab. 2 Overview Connection and control elements................... Tab. 3 LEDs at power on........................... Tab. 4 Function VCC LED..........................Tab. 5 Function NET ST - LED .........................
Introduction | 1 1 Introduction The described devices, accessories, hardware and/or software are products of KEB Automation KG. The enclosed documents correspond to conditions valid at printing. Misprint, mistakes and technical changes reserved. 1.1 Markings 1.1.1 Warnings Certain operations can cause hazards during the installation, operation or there- after.
Lexicon entry 1.2 Laws and guidelines KEB Automation KG confirms with the CE mark and the EU declaration of conform- ity, that our device complies with the essential safety requirements. The EU declaration of conformity can be downloaded on demand via our website.
Introduction | 1 Other wordmarks and/or logos are trademarks (™) or registered trademarks (®) of their respective owners. 1.6 Validity of this manual This part of the instruction manual describes the implemented control card. It • is only valid in conjunction with the instructions for use of the power part. •...
2 | General Safety Instructions KEB Automation KG 2 General Safety Instructions The products are developed and built according to the state of the art and recog- nized safety rules. Nevertheless, their use may create dangers to life and limb of the user or third parties or damage to the machine and other material property.
General Safety Instructions | 2 2.2 Start-up and operation The start-up (i.e. the starting of normal operation) is prohibited until the machinery has been proved to conform to the provisions Directive 2006/42/EG Directive 2014/30/EU; EN 60204-1 must be observed. Wrong parameterization WARNUNG Unintentional behaviour of the drive ü...
3 | Product description KEB Automation KG 3 Product description 3.1 Description of the control board PRO Die Steuerkarte PRO stellt folgende Grundfunktionen zur Verfügung: • Digital and analog inputs and outputs • Serial diagnostic interface for connection to a PC • Hardware of the control circuit „safety separated“ according to EN 61800-5-1 •...
3 | Product description KEB Automation KG 3.4 Connection and control elements Temperature monitoring, brake control/ monitoring Control terminal block for digital in- puts/outputs; 24V supply; relay out- put;analog inputs and outputs;CAN Safety module Encoder interface channel A Encoder interface channel B...
Product description | 3 • 2 control inputs for brakes or relays • 1 analog input for temperature detection 3.6 Control terminal strip X2A The control terminal strip X2A is a 28-pole pluggable, double-row terminal strip with spring-cage connection. It contains: •...
3 | Product description KEB Automation KG LEDs Status Note Device off Initialization Control is supplied with 24 V ready for operation Device is ready for operation and the LEDs start with their normal function (approx. 3 s) Tab. 3: LEDs at power on 3.13.2 VCC - LED...
Connection of the control | 4 4 Connection of the control Observe the following instructions to avoid malfunctions! • Install control cables and power cables separately (approx. 10…20 cm distance); Lay crossings in a right angle. • In case of inductive load on the relay outputs a protective wiring must be provided (e.g.
4 | Connection of the control KEB Automation KG 4.2 Terminal strip X2A Name Description DI1 / AN3 Digital input 1 / analog input 3 (switchable via software) Digital input 2 Digital input 3 Digital input 4 Digital input 5 Digital input 6 Digital input 7 (fast input =>...
Connection of the control | 4 Terminals X2A.1…X2A.8 Classification Type 3 in accordance with DIN EN 61131-2 Low level (logical 0) -3 … +5 V / 3 mA High level (logical 1) 11 … 30 V / 2 … 6 mA Special features DI1 is switchable via software as analog input AN3.
4 | Connection of the control KEB Automation KG Connection Connection appliance Connection external control 10 12 ext. 4.2.3 Relay output; 4.2.3.1 Relay output 2-pole Specification safe relay 2-pole Number with positive-driven contacts Name Terminals X2A.14; X2A.15 Type 2-pole, NO contact Switching voltage (rated) DC 24 V...
Connection of the control | 4 Connection safe relay 2-pole with Connection safe relay 2-pole with positive-driven contacts positive-driven contacts 4.2.4 Analog input 4.2.4.1 Differential input No potential separation of the analog inputs to the control voltage! ACHTUNG Malfunction or defect caused by voltage differences. a) A potential equalizing line between analog value source and analog input is re- quired if the analog value is outside the common mode range.
4 | Connection of the control KEB Automation KG 4.2.4.2 Absolute input Specification (absolute input) Number Name Terminals X2A.1 switchable via software as digital/ analog input) Classification non-isolated absolute input Input signals Voltage Voltage input DC 0.2…10 V / max. 5 mA Others Is not intended for control with poten- tiometer.
Connection of the control | 4 • externally by a central 24V supply. To select a suitable voltage source, the maximum current consumption must al- ways be determined. 4.2.6.1.1 Determination of the current consumption The input P24Vin (X2A.28) supplies following components: •...
Page 24
4 | Connection of the control KEB Automation KG 4.2.6.2 Voltage output to supply the inputs Specification voltage output Name 24Vout 0V (reference potential) Terminals X2A.16, X2A.26 (24Vout) X2A.27 (0V) Output current max. 100 mA (short-circuit proof) total for both terminals Output voltage minimum P24Vin –...
The safety module type 5 includes the following functions: STO, SBC, SS1-r, SS1-t, SLS, SSM, SMS, SLA, SDLC Safety over EtherCAT® The description of the functions is given in the safety manual at the following link: Safety manual type 5 https://www.keb.de/fileadmin/media/Manuals/dr/ ma_dr_safety-typ5-20191137_en.pdf ma_dr_s6-cu-p-inst-20156056_en...
6 | Diagnosis/visualisation X4A KEB Automation KG 6 Diagnosis/visualisation X4A The integrated serial interface provides the following functions: • Parameterization of the device with the KEB software COMBIVIS. • Connection of a control operator. • DIN66019II as communication protocol. Interface Specification RS485 Common-mode voltage range 0…12 V...
USB port of personal computers. The USB-serial converter is internal electrically isolated. 6.4 Connection of the RS485 interface RS485 interface supports half-duplex and duplex operation. Wiring examples can be found in the following link: Wiring examples can be found under the following link: https://www.keb.de/fileadmin/media/Techinfo/dr/tn/ ti_dr_tn-rs485-connection-00002_en.pdf ma_dr_s6-cu-p-inst-20156056_en...
7 | Fieldbus interfaces KEB Automation KG 7 Fieldbus interfaces 7.1 Type code fieldbus A CAN interface is integrated in the control unit as standard. Other fieldbus inter- faces are identified by the 9th digit of the material number. 9. digit Control board variant PRO | Multi-Encoder-Interface, CAN®, Ethernet-Fieldbus-Interface,...
Fieldbus interfaces | 7 Light pattern NET ST LED (red/ Status Light pattern Description green combination) Pre-Op g-0 (grid 200 ms) Device in PRE-OPERA- TIONAL status Stop g-0-0-0-0-0 (grid 200 ms) Device in STOPPED status g (permanent) Device in OPERATIONAL status; no error Bus off r (permanent) CAN bus switched off.
7 | Fieldbus interfaces KEB Automation KG Common-mode voltage range 0…12 V to GND Potential separation Potential-free to control potential. Bus termination Integrated 121 Ω Connection X4B Name Function TxD-A Transmission signal A TxD-B Transmission signal B Reference potential RxD-A Receive signal A Abb. 5: RJ45 socket front view...
Encoder interfaces | 8 8 Encoder interfaces 8.1 Type code encoder interface A CAN interface is integrated in the control unit as standard. Other fieldbus inter- faces are identified by the 9th digit of the material number: 9. digit Control board variant PRO | no encoder interface, CAN®, Ethernet fieldbus interface, safe relay PRO | Multi encoder interface, CAN®, Ethernet fieldbus interface, safe re- 8.2 Multi-Encoder-Interface...
8 | Encoder interfaces KEB Automation KG voltage supply - min. encoder voltage max. encoder cable length = max. encoder current • 2 • wire resistor per meter Abb. 7: Encoder cable length The supply voltage depends on the set encoder. The other values can be found in the data sheet of the encoder and the encoder cable.
9 | Brake control and temperature detection KEB Automation KG 9 Brake control and temperature detection Name Notes Brake control / output Brake control / output For supplying the feedback inputs P24Vin - 0.5V / max. 1A 24Vout (BR+ and 24Vout in total 2A)
Brake control and temperature detection | 9 Connection = 24 V = 2 A _max Abb. 8: Connection of a brake 9.2 Temperature detection Electric shock by sensors without protective separation! GEFAHR a) Only use sensors with basic insulation. b) Only sensors with double insulation (basic insulation plus additional insulation) are permitted up to the specified year/week of manufacturing (see specifica- tion).
9 | Brake control and temperature detection KEB Automation KG Operating mode (dr33) Resistance Temperature/state PT1000 1 kΩ 0 °C 1.38 kΩ 100 °C 1.75 kΩ 200 °C Monitoring <0.04 kΩ Short circuit > 79.5 kΩ No connection (sensor break) 9.2.1 Operation without temperature detection Use of the COMBIVERT without evaluation of the temperature input: Switch off evaluation (pn12 =7) or install bridge between terminal TA1 (X1C.9) and...
Brake control and temperature detection | 9 Mixed sensor chain ① ① Connection via shield bracket (if not available, place on mounting plate). Tab. 20: Connection examples ma_dr_s6-cu-p-inst-20156056_en...
10 | Revision History KEB Automation KG 10 Revision History Edition Version Note 2018-12 Pre-series version. 2019-07 Series version 2022-10 Function yellow LED EtherCAT changed; Editorial changes due to conversion to editorial system. 2022-11 Encoder interface pin 19 changed ma_dr_s6-cu-p-inst-20156056_en...
Glossary Glossary Application EN 61800-5-1 The application is the intended use of the KEB Adjustable speed electrical power drive systems. product. Part 5-1: Safety requirements - Electrical, thermal and energy requirements (VDE 0160-105-1, IEC 61800-5-1) Autonegotiation Procedure for determining the max. transmission EnDat speed.
Page 44
Glossary KEB Automation KG Safe brake control SDLC Safe Door Lock Control SELV Safe protective extra-low voltage (unearthed; <60V). SinCos Incremental encoder with sinusoidal signals. Safely-limited acceleration Safely-limited speed Safe maximum speed SS1-r Safe Stop 1 ramp monitored (with deceleration ramp monitoring;...