4.2.4 Analog input
4.2.4.1 Differential input
NOTICE
Specification (differential inputs)
Connection
4.2.4.2 Absolute input
Specification (absolute input)
ma_dr_s6-cu-a-inst-20109645_en
No potential separation of the analog inputs to the control voltage!
Malfunction or defect caused by voltage differences.
a) A potential equalizing line between analog value source and analog input is re-
quired if the analog value is outside the common mode range.
b) Connect potential equalizing line with 0V of the control terminal block.
Number
Name
Terminals
Classification
Input signals
Voltage input
Current input
Common mode range
Connection of the analog differential inputs AN1 and AN2
0...±20mA
4...20mA
*) Equipotential bonding conductor
Number
Name
Terminals
Classification
Input signals
Voltage input
Others
Connection of the control | 4
2
AN1, AN2
X2A.18 (AN1)
X2A.20 (AN2)
Non-isolated differential input
Current/voltage switchable
DC 0...±10 V
DC 0...±20 mA; DC 4...20 mA
-12.5 V...17.5 V
18
20 22
17
19
21
*
+
+
0...±10Vdc
1
AN3
X2A.1 switchable via software as digital/

analog input)

non-isolated absolute input
Voltage
DC 0.2...10 V / max. 5 mA
Is not intended for control with poten-
tiometer. The voltage source must be
able to supply the input current.
21