4-3-2-4. External Test Input

F3SG-SRA
F3SG-SRB
First, carry out 4-3-1. Preparing to Change Settings.
Next, on the Top page, click the icon below.
The setting screen below is displayed.
No.
Function name
1
External Test Signal
Inversion
By setting either enable or disable of the external test signal inversion to PNP/NPN selection, the
condition to stop emission can be selected. Refer to the table below.
External Test Signal Inversion *1
Disable (factory default setting)
Enable
*1. This can be set using SD Manager 3.
*2. This can be set by wiring.
For more information on external test signal inversion, refer to 2-6. External Test.
When changing the settings is complete, confirm the settings and write the configuration to the F3SG-SR/PG.
To enable the written configuration, refer to 4-2-7-3. Writing Configuration into Intelligent Tap.
When connecting the Intelligent Tap to a F3SG-SR/PG and trying to return the F3SG-SR/PG to [Detecting], follow step 4
of 4-1-3-2. Connection Procedure When Using USB Connector to restart the F3SG-SR/PG and Intelligent Tap, or click
the [Monitor]
F3SG-PGA-A
F3SG-PGA-L
Description
Set either enable or disable of the external test signal
inversion.
PNP setting *2
Emission stops by connecting with 24 V
connection.
Emission stops by connecting with 0 V
connection.
button.
Setting with SD Manager 3
F3SG-PGA-C
Disable Enable/Disable
Input voltage
Emission stops by connecting with 0 V
Emission stops by connecting with 24 V
Initial
Configurable value
value
or numerical range
NPN setting *2
connection.
connection.
F3SG-SR/PG
User's Manual
E
235