2-15-3. Setting with Intelligent Tap
Fixed blanking can be configured using Positions 6 and 7 of the DIP Switch of the Intelligent Tap.
The Fixed Blanking Monitoring function is configured as Lockout.
Make sure the Position 2 of the DIP Switch is set at ON (DIP Switch Enabled) to activate the settings by the DIP Switch.
Refer to Chapter 3 Setting with Intelligent Tap for more information on setting this function by the Intelligent Tap.
2-15-4. Setting with SD Manager 3
The user can make changes to the settings of this function by the SD Manager 3.
Setting is required for each sensor segment in case of a cascade connection.
Function
Fixed Blanking
Fixed Blanking
Bottom beam
zone
Top beam
Fixed Blanking Monitoring
Number of allowable upper beams
Number of allowable lower beams
It is recommended that the Position 2 of the DIP Switch be set at OFF (DIP Switch Disabled).
Setting the Fixed Blanking Monitoring function to Disable Monitoring may create an undetectable area where a person
can block the F3SG-SR without being detected, and it is not compliant with IEC 61496-2. Conduct risk assessment
analysis thoroughly before enabling this setting.
Refer to 4-3-4-1. Fixed Blanking for more information on setting this function by the SD Manager 3.
Initial value
Disable
1
1
Lockout
0 beam
0 beam
System Operation and Functions
Configurable value or numerical range
Enable/Disable
any beam in 1-beam increments
any beam in 1-beam increments
Lockout/Disable monitoring/Cancel blanking zone/
Quick blanking
0 to 5 beams in 1-beam increments
0 to 5 beams (1-beam increments)
E
F3SG-SR/PG
113
User's Manual