6-2-1-2. Auto Reset Mode with Wired Synchronization and EDM Unused
F3SG-SRA
F3SG-SRB
[Wiring Example (F3SG-SR and F3SG-PGA-A/-L)]
F39-JGC-L
Function
EDM
Interlock
Operating Range Selection
Non-Muting system
External Test not used
Optical Synchronization
Timing chart
Beam state: Unblocked
Blocked
OSSD
• When a functional earth is necessary, wire an earth cable according to the example in 6-2-1-1. Auto Reset Mode with
Optical Synchronization and EDM Unused. Also refer to 5-4-4. Functional Earth Connection for more information.
F3SG-PGA-A/-L
F3SG-PGA-C
F39-JGC-D
EDM Disabled (factory default setting)
Auto Reset (factory default setting)
Long (factory default setting)
Perform wiring according to the wiring diagram.
Connect the TEST line of the emitter to 0V/24V of the emitter.
Connect the COM(+) and COM(-) line of the emitter and receiver with each other.
*1. Reverse the polarity of the power supply when using in the NPN system. Select a safety controller
of PNP or NPN type according to the system of your application.
*2. Refer to 2-6. External Test for more information if External Test is used.
*3. Connect the line to 24V/0V (brown) of the receiver via a lockout reset switch (NC contact) if
Lockout Reset is used.
*4. Refer to 6-3. Connectable Safety Control Units for moreinformation.*6
*5. The safety controller and the F3SG-SR/PG must share the power supply or be connected to the
common terminal of the power supply.
*6. This is the case for a PELV circuit.
Input/Output Circuit and Applications
Intelligent Tap
*6
IN1
IN2
Safety controller
*4 *5
Setting
Not Needed
Wiring for NPN *1
24 VDC
24 VDC
F3SG-SR/PG
User's Manual
E
385