Modbus Address Tables; Data Types And Access Types; Central Processing Unit Addresses - JUMO mTRON T Manual

Measuring,control, and automation system
Hide thumbs Also See for mTRON T:
Table of Contents

Advertisement

NOTE!
These tables are important for external devices that access the central processing unit as a
Modbus master (configured as a Modbus slave). Alternatively, external devices can also ac-
cess the cenral processing unit using the Modbus frames.
7.1

Data types and access types

Data types
Bit x
Bit no. x (bit 0 is the lowest bit)
Boolean
Boolean value (TRUE or FALSE) can be read or written as a word. The value range is 0 to 1.
Byte
1 byte = 8 bi, can be read or written as word. The value range is 0 to 255.
Word
1 Word = 2 bytes = 16 bits
Int32
Integer (32 bits) = 2 words
Uint32
Unsigned integer (4 bytes) = 32 bits = 2 words
Long
Long integer (4 bytes) 32 bits = 2 words
Float
Floating point value (4 bytes) acc. to IEEE 754
Char[60]
Text with 60 characters, each with 2 characters in a word
Bit field 32 Bit field 32 bits long
Access types
R/O
Read only
W/O
Write only
R/W
Read write
CAUTION!
Write operations to some R/W parameters result in them being saved to the EEPROM or
Flash memory.
The storage components have only a limited number of writing cycles (approx. 10,000 or
100,000), which is why no fast cyclical writing operations should be performed, since there
is otherwise a risk of a storage error in case of a power failure.
7.2

Central processing unit addresses

The following tables contain specifications of all process and device data for the central pro-
cessing unit including their address, data type, and type of access.
Central processing unit - cycle time and device name
Address
Hex.
Dec.
0x000A
10
0x009D
157
0x00B0
176
Data type/
Access Signal designation
bit number
Long
R/O
Uint32
R/O
Uint32
R/O

7 Modbus address tables

Software version
Modbus master TCP device 1: actual cycle time in 5 ms ticks
Modbus master TCP device 2: actual cycle time in 5 ms ticks
77

Advertisement

Table of Contents
loading

Table of Contents