Examples - IBM 7133 D40 Service Manual

Serial disk systems
Hide thumbs Also See for 7133 D40:
Table of Contents

Advertisement

-B card=mode
-S
-S d[drive_bay ...]
-S b[card ...]
-S p[PSU ...]
-S r
-S c
-S o
-T threshold=value

Examples

v To display the status of all bypass cards on enclosure0, give the command:
ssaencl -l enclosure0 -b
v To display the status and VPD of the controller card in enclosure0, give the
command:
ssaencl -l enclosure0 -c -v
v To modify the ID for enclosure0 to R2D2, give the command:
ssaencl -l enclosure0 -I R2D2
v To display the contents of disk bay (slot) 8 in enclosure0, give the command:
ssaencl -l enclosure0 -d 8
268
7133 Models D40 and T40 Service Guide
Modifies the specified bypass cards to be in the given modes. The valid values
for the mode parameter are:
v Automatic
v Bypass
v Inline
v Open
Valid values for the card parameter are 1, 4, 5, 8, 9, 12, 13, 16.
Resets the "exchanged" flag of the selected FRU.
Resets the flag for the selected drive bay. Valid values for drive_bay are 1, 2,
3, and so on.
Resets the flag for the bypass card. Valid values for card are 1, 4, 5, 8, 9, 12,
13, 16.
Resets the flag for the selected PSU. Valid values for PSU are 1, 2.
Resets the flag for the remote power-on control (RPO).
Resets the flag for the controller card.
Resets the flag for the operator panel.
Modifies the specified temperature thresholds to the given values. The valid
values for the [threshold] parameter are:
lowarn
The low-temperature warning threshold.
hiwarn
The high-temperature warning threshold.
The value parameter is a temperature in degrees C.