Memory Areas
Area
PC
Work bits
SP10
SP16
SP20
Dedicated bits
SP10
SP16,
SP20
Data Retention
All
(DR)
Link Relay
All
(LR)
Timer/Counter
All
(TC)
3-2-1

Data Area Structure

28
No. of
Word
Bit
bits
addresses
addresses
36
00
0008 to 0015
01
0104 to 0115
02
0200 to 0215
208
00
0010 to 0015
01
0106 to 0115
02
0200 to 0215
10 to 20
1000 to 2015
204
00
0012 to 0015
01
0108 to 0115
02
0200 to 0215
10 to 20
1000 to 2015
20
03
0300 to 0315
04
0408 to 0411
69
03
0300 to 0315
04
0408 to 0411
05
0515
07
0700 to 0715
08
0800 to 0815
09
0900 to 0915
256
DR 00 to
DR 0000 to
max.
DR 15
DR 1515
128
LR 00 to
LR 0000 to
max.
LR 07
LR 0715
16
TIM/CNT 00 to 15
When designating a data area, the acronym for the area is always required
for the DR, TC, and LR areas.
An actual data within any data area but the TC area is designated by its ad-
dress. The address designates the bit or word within the area where the de-
sired data is located. The TC area consists of TC numbers, each of which is
used for a specific timer or counter defined in the program. Refer to 3-2-7 TC
(Timer/Counter) Area for more details on TC numbers.
The rest of the data area consists of words, each of which consists of 16 bits
numbered 00 through 15 from right to left. words 000 and 001 are shown be-
low with bit numbers. Here, the content of each word is shown as all zeros.
Bit 00 is called the rightmost bit; bit 15, the leftmost bit.
The term least significant bit is often used for rightmost bit; the term most
significant bit, for leftmost bit. These terms are not used in this manual be-
cause a single data word is often split into two or more parts, with each part
used for different parameters or operands. When this is done, the rightmost
bits of a word may actually become the most significant bits, i.e., the leftmost
bits in another word, when combined with other bits to form a new word.
Function
These bits are used within the program to aid
programming.
These bits are assigned specific functions.
For details, refer to the table in 3-2-4 Dedicated Bits.
These bits retain their ON/OFF state even during power
interruptions. The number of DR bits decreases if more
link bits are designated.
Used to exchange data with other SP-series PCs
through a Link Adapter. To access the LR area, the LR
area must be defined via the Programming Console.
Used to define timers and counters and to access
Completion Flags, PV, and SV for them. TC 14 is used
by the HIGH-SPEED TIMER instruction (TIMH), and TC
15 is used by the ANALOG TIMER instruction.
Section 3-2