Wiring inputs and outputs

Wiring sensors to the TV-VVTZC-E2's inputs

You can wire the following sensors to the TV-VVTZC-E2's inputs:
Alternate space temperature sensor (page 33)
Supply Air Temperature sensor (page 33)
Duct Air Temperature sensor (page 34)
CO
sensor (page 34)
2
Relative Humidity sensor (page 37)
Remote occupancy contact sensor (page 38)
NOTE This document gives instructions for wiring the sensors to the TV-VVTZC-E2. For detailed installation
instructions, see the device's Installation Guide.
WARNING Disconnect electrical power to the TV-VVTZC-E2 before wiring it. Failure to follow this warning
could cause electrical shock, personal injury, or damage to the controller.
CAUTION
Do not run sensor or relay wires in the same conduit or raceway with Class 1 AC or DC service wiring.
Do not abrade, cut, or nick the outer jacket of the cable.
Do not pull or draw cable with a force that may harm the physical or electrical properties.
Avoid splices in any control wiring.

Wiring specifications

Cable from sensor to controller:
Maximum length:
TruVu™ VVTZC-E2
Installation and Start-up Guide
If <100 ft (30.5 meters)
If >100 ft (30.5 meters)
500 feet (152 meters)
32
22 AWG, unshielded
22 AWG, shielded