Wireless sensor overview

The Carrier wireless sensors, designed for zone control, are low-power wireless devices that use light-harvesting
through solar panels as their primary power source. The wireless line of sensors includes the models shown in the
list below. All are available in 868, 902, and 928 MHz radio frequency. The sensors are thermistor-based
temperature sensors that may optionally sense humidity.
Wireless sensors communicate through a Wireless Adapter, which is wired to the Rnet port of the controller.
REQUIREMENTS
A v6.5 or later i-Vu® system
v6-xx-xxx or later controller drivers
The following is a list of all available wireless devices:
Standard
Plus
Pro-F
Motion/Lux Sensor
Window/Door Sensor
Adapter
To configure the control program for the desired user interaction with the sensor, see the Wireless Sensors
Application Guide. For detailed instructions, see the Wireless Sensors Installation Guide.

To install the Wireless Adapter for wireless sensors

WARNING Do not apply line voltage (mains voltage) to the Wireless Adapter.
To wire, power, and mount the Wireless Adapter
NOTES
The Wireless Adapter requires a 24 Vac or 24 Vdc power supply. It is not powered by the Rnet.
If the Wireless Adapter will be:
Daisy-chained on the Rnet with ZS sensors or an Equipment Touch, use the standard 4-conductor Rnet
wiring.
The only device on the Rnet, you can use a 3-conductor cable instead of the standard 4-conductor Rnet
cable.
MPC Open XP
MPC Open XP IO48/816
Installation and Start-up Guide
Carrier Proprietary and Confidential
23
Installing the MPC Open XP
CARRIER CORPORATION ©2017