UPS status after blade shutdown
Select either of "Put UPS running on battery to sleep" or "Put all UPS to temporarily
sleep" when the EM card shuts down the CPU blade because the number of healthy UPSs
has decreased due to input power lost.
The UPS is put in temporarily sleep state for 6 minutes.
The default setting is "Put UPS running on battery to sleep". You need not to change in
usual case.
NOTE:
While the Web console of the UPS is open or the command
line console of the UPS is connected, the sleep feature is unavailable.
UPS Sleep Delay
Specify the time until the UPS actually enters into sleep state after the sleep command is
issued to UPS, in the unit of second. Available value depends on the UPS model. See the
table below. The default setting is 90 seconds.
If an illegal value is specified for the relevant UPS, the longest time allowed for that UPS
is set.Ex.) If "120" is specified for N8142-29, "630" seconds is set.
UPS model
N8142-11B
N8142-23A
N8142-24A
N8142-25/25A
N8142-29
N8142-31
N8142-35
N8142-38
N8142-42
IMPORTANT:
N8142-38 and N8142-42. It needs to be set using the web console of
the SNMP card. See "Setting UPS Sleep Delay on N8142-38 and
N8142-42" below for instructions.
Setting UPS Sleep Delay on N8142-38 and N8142-42
Open the Status screen of the EM Card web console and click the HTTP button on the list
of UPS.
Allowable value (seconds)
20
180
300
0
90
180
0
20
60
0
20
60
0
90
180
0
90
180
0
20
60
0
90
180
0
90
180
UPS Sleep Delay can not be set from the EM Card for
-
245
600
270
360
120
240
120
240
270
360
270
360
120
240
270
360
270
360
-
450
540
630
480
720
960
480
720
960
450
540
630
450
540
630
480
720
960
450
540
600
450
540
600