ABB Relion 650 Series Applications Manual page 79

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 505 287-UUS B
ANSI09000636 V1 EN-US
Figure 28: Directional function characteristic
1.
RCA = Relay characteristic angle 55°
2.
ROA = Relay operating angle 80°
3.
Reverse
4.
Forward
7.1.3.1
Settings for steps 1 to 4
DirModeSelx : The directional mode of step x . Possible settings are Disabled / Non-directional /
Forward / Reverse .
Characteristn : Selection of time characteristic for step n . Definite time delay and different types of
inverse time characteristics are available according to table 10. Step 2 and 3 are always definite
time delayed.
Busbar protection REB650
Application manual
3
2
n means step 1 and 4. x means step 1, 2, 3 and 4.
© Copyright 2013 ABB. All rights reserved
V
ref
1
2
4
I
dir
ANSI09000636-1-en.vsd
Section 7
Current protection
M12982-19 v6.1.1