ABB Relion 650 Series Applications Manual page 193

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 505 287-UUS B
11.8
Integer to boolean 16 conversion with logic node
representation IB16FCVB
11.8.1
Identification
Function description
Integer to boolean 16 conversion
with logic node representation
11.8.2
Application
Integer to boolean 16 conversion with logic node representation function (IB16FCVB) is used to
transform an integer into a set of 16 binary (logical) signals. IB16FCVB function can receive an
integer from a station computer – for example, over IEC 61850–8–1. These functions are very useful
when the user wants to generate logical commands (for selector switches or voltage controllers)
by inputting an integer number. IB16FCVB function has a logical node mapping in IEC 61850.
11.8.3
Settings
The function does not have any parameters available in the local HMI or Protection and Control IED
Manager (PCM600)
11.9
Elapsed time integrator with limit transgression and
overflow supervision TEIGGIO
11.9.1
Identification
Function Description
Elapsed time integrator
11.9.2
Application
The function TEIGGIO is used for user defined logics and it can also be used for different purposes
internally in the IED . An application example is the integration of elapsed time during the
measurement of neutral point voltage or neutral current at earth fault conditions.
Settable time limits for warning and alarm are provided. The time limit for overflow indication is
fixed.
Busbar protection REB650
Application manual
IEC 61850
identification
IB16FCVB
IEC 61850
identification
TEIGGIO
© Copyright 2013 ABB. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
IEC 60617
ANSI/IEEE C37.2 device
identification
number
-
-
Section 11
Logic
SEMOD167944-2 v3
SEMOD158512-5 v4
ABBD8E195017 v4
GUID-DB37ECF3-9189-46A5-89BD-6FE39613EF7E v1
GUID-1913E066-37D1-4689-9178-5B3C8B029815 v1
GUID-B4B47167-C8DE-4496-AEF1-5F0FD1768A87 v1
187

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reb650