ABB Relion 650 Series Applications Manual page 150

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 10
Control
289OPTR(22089OTR)(bay 1/sect.B1)
289PTR (22089OTR)(bay n/sect.B1)
VP289TR(V22089TR) (bay 1/sect.B1)
VP289TR(V22089TR) (bay n/sect.B1)
EXDU_BB (bay 1/sect.B1)
EXDU_BB (bay n/sect.B1)
ANSI04000508 V1 EN-US
Figure 59: Signals from any bays in section B1 to a busbar grounding switch in the same
For a busbar grounding switch, these conditions from the B2 busbar section are valid:
289OPTR(22089OTR) (bay 1/sect.B2)
289OPTR(22089OTR) (bay n/sect.B2)
VP289TR(V22089TR) (bay 1/sect.B2)
VP289TR(V22089TR) (bay n/sect.B2)
EXDU_BB (bay 1/sect.B2)
EXDU_BB (bay n/sect.B2)
ANSI04000509 V1 EN-US
Figure 60: Signals from any bays in section B2 to a busbar grounding switch in the same
For a busbar grounding switch on bypass busbar C, these conditions are valid:
144
. . .
. . .
. . .
DCOPTR (B1/B2)
. . .
. . .
. . .
VPDCTR (B1/B2)
. . .
. . .
. . .
EXDU_DC (B1/B2)
section
. . .
. . .
. . .
DCOPTR (B1/B2)
. . .
. . .
. . .
VPDCTR (B1/B2)
. . .
. . .
. . .
EXDU_DC (B1/B2)
section
© Copyright 2013 ABB. All rights reserved
BB_DC_OP
AND
VP_BB_DC
AND
EXDU_BB
AND
en04000508_ansi.vsd
BB_DC_OP
AND
VP_BB_DC
AND
EXDU_BB
AND
en04000509_ansi.vsd
Busbar protection REB650
1MRK 505 287-UUS B
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reb650

Table of Contents