ABB Relion 650 Series Applications Manual page 203

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 505 287-UUS B
Table 18:
Setting
PMin
PMax
PZeroDb
PRepTyp
PDbRepInt
PHiHiLim
PHiLim
PLowLim
PLowLowlLim
PLimHyst
Table 19:
Setting
IMagComp5
IMagComp30
IMagComp100
VAmpComp5
VMagComp30
VMagComp100
IAngComp5
IAngComp30
IAngComp100
Busbar protection REB650
Application manual
Settings parameters for level supervision
Short Description
Minimum value
Minimum value
Zero point clamping in 0.001%
of range
Reporting type
Cycl: Report interval (s), Db: In
% of range, Int Db: In %s
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Hysteresis value in % of range
(common for all limits)
Settings for calibration parameters
Short Description
Magnitude factor to calibrate
current at 5% of In
Magnitude factor to calibrate
current at 30% of In
Magnitude factor to calibrate
current at 100% of In
Magnitude factor to calibrate
voltage at 5% of Vn
Magnitude factor to calibrate
voltage at 30% of Vn
Magnitude factor to calibrate
voltage at 100% of Vn
Angle calibration for current at
5% of In
Angle pre-calibration for
current at 30% of In
Angle pre-calibration for
current at 100% of In
© Copyright 2013 ABB. All rights reserved
Selected
Comments
value
-100
Minimum expected load
100
Maximum expected load
3000
Set zero point clamping to 45 MW that is, 3% of
200 MW
db
Select magnitude deadband supervision
2
Set ±Δdb=30 MW that is, 2% (larger changes than
30 MW will be reported)
60
High alarm limit that is, extreme overload alarm
50
High warning limit that is, overload warning
-50
Low warning limit. Not active
-60
Low alarm limit. Not active
2
Set ±Δ Hysteresis MW that is, 2%
Selected
Comments
value
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
Section 12
Monitoring