1MRK 505 287-UUS B
789OPTR (bay 1)
. . .
. . .
. . .
789OPTR (bay n)
VP789TR (bay 1)
. . .
. . .
. . .
VP789TR (bay n)
EXDU_BB (bay 1)
. . .
. . .
. . .
EXDU_BB (bay n)
ANSI04000510 V1 EN-US
Figure 61: Signals from bypass busbar to busbar grounding switch
10.3.4.3
Signals in double-breaker arrangement
The busbar grounding switch is only allowed to operate if all disconnectors of the bus section are
open.
(WA1)A1
(WA2)B1
ANSI04000511 V1 EN-US
Figure 62: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BB_DC_OP
VP_BB_DC
EXDU_BB
These signals from each double-breaker bay (DB_BUS) are needed:
Signal
189OPTR
289OPTR
VP189TR
VP289TR
EXDU_DB
Busbar protection REB650
Application manual
Section 1
Section 2
A1A2_DC(BS)
B1B2_DC(BS)
BB_ES
DB_BUS
DB_BUS
All disconnectors of this part of the busbar are open.
The switch status of all disconnectors on this part of the busbar are valid.
No transmission error from any bay that contains the above information.
189 is open.
289 is open.
The switch status of 189 is valid.
The switch status of 289 is valid.
No transmission error from the bay that contains the above information.