ABB Relion 650 Series Applications Manual page 135

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

1MRK 505 287-UUS B
Operation of primary apparatuses
Select-Execute principle to give high security
Selection function to prevent simultaneous operation
Selection and supervision of operator place
Command supervision
Block/deblock of operation
Block/deblock of updating of position indications
Substitution of position indications
Overriding of interlocking functions
Overriding of synchronism check
Operation counter
Suppression of Mid position
The apparatus control function is realized by means of a number of function blocks designated:
Switch controller SCSWI
Circuit breaker SXCBR
Circuit switch SXSWI
Position evaluation POS_EVAL
Select release SELGGIO
Bay control QCBAY
Local remote LOCREM
Local remote control LOCREMCTRL
SCSWI, SXCBR, QCBAY and SXSWI are logical nodes according to IEC 61850. The signal flow
between these function blocks appears in figure 49. The function Logical node Interlocking
(SCILO) in the figure
Control operation can be performed from the local IED HMI. If the administrator has defined users
with the UMT tool, then the local/remote switch is under authority control. If not, the default
(factory) user is the SuperUser that can perform control operations from the local IED HMI without
LogOn. The default position of the local/remote switch is on remote.
Busbar protection REB650
Application manual
49
is the logical node for interlocking.
© Copyright 2013 ABB. All rights reserved
Section 10
Control
129