module inputs as follows. In the functional block diagram, 0 and 1 are designated 0=FALSE and
1=TRUE:
789_OP = 1
789_CL = 0
7189G_OP = 1
7189G_CL = 0
BB7_D_OP = 1
BC_17_OP = 1
BC_17_CL = 0
BC_27_OP = 1
BC_27_CL = 0
EXDU_BPB = 1
VP_BB7_D = 1
VP_BC_17 = 1
VP_BC_27 = 1
If there is no second busbar WA2 and therefore no 289 disconnector, then the interlocking for 289
is not used. The state for 289, 2189G, BC_12, BC_27 are set to open by setting the appropriate
module inputs as follows. In the functional block diagram, 0 and 1 are designated 0=FALSE and
1=TRUE:
289_OP = 1
289_CL = 0
2189G_OP = 1
2189G_CL = 0
BC_12_CL = 0
BC_27_OP = 1
BC_27_CL = 0
VP_BC_12 = 1
10.3.11
Interlocking for transformer bay AB_TRAFO (3)
10.3.11.1
Application
The interlocking for transformer bay (AB_TRAFO, 3) function is used for a transformer bay
connected to a double busbar arrangement according to figure 92. The function is used when
there is no disconnector between circuit breaker and transformer. Otherwise, the interlocking for
line bay (ABC_LINE, 3) function can be used. This function can also be used in single busbar
arrangements.
Busbar protection REB650
Application manual
© Copyright 2013 ABB. All rights reserved
Section 10
Control
IP14149-1 v2