Accepted originator categories for PSTO
If the requested command is accepted due to the authority allocation control, the respective value
will change. Otherwise the attribute
PSTO value is changed under a command, then the command is reset.
The accepted originator categories for each PSTO value are shown in
Table 15:
PermittdSourceToOperate
0 = Off
1 = Local
2 = Remote
Table continues on next page
130
SCSWI
SCILO
(3)
SCSWI
SCILO
(3)
The IEC 61850 communication has always priority over binary inputs, e.g. a block
command on binary inputs will not prevent commands over IEC 61850.
Accepted originator categories for each PSTO
© Copyright 2013 ABB. All rights reserved
IEC 61850
SXCBR
SXSWI
blocked-by-switcing-hierarky is set in the cause signal. If the
Originator
4,5,6
1,4,5,6
2,3,4,5,6
1MRK 505 287-UUS B
-189
-BKR1
52
-989
ANSI10000198_2_en.vsd
Table 15
Busbar protection REB650