1MRK 505 287-UUS B
16.3
SNTP server requirements
16.3.1
SNTP server requirements
The SNTP server to be used is connected to the local network, that is not more than 4-5 switches
or routers away from the IED. The SNTP server is dedicated for its task, or at least equipped with a
real-time operating system, that is not a PC with SNTP server software. The SNTP server should be
stable, that is, either synchronized from a stable source like GPS, or local without synchronization.
Using a local SNTP server without synchronization as primary or secondary server in a redundant
configuration is not recommended.
Busbar protection REB650
Application manual
© Copyright 2013 ABB. All rights reserved
Section 16
Requirements
GUID-588FCD12-C494-445E-8488-8287B34EFD9A v3
247