Section 12
Monitoring
800/5 A
380kV 120V
/
3
ANSI09000039 V1 EN-US
Figure 100: Single line diagram for 380kV OHL application
In order to monitor, supervise and calibrate the active and reactive power as indicated in figure
100
it is necessary to do the following:
1.
Set correctly CT and VT data and phase angle reference channel
for analog input channels
2.
Connect, in PCM600, measurement function to three-phase CT and VT inputs
3.
Set under General settings parameters for the Measurement function:
Table 17:
Setting
Operation
PowMagFact
PowAngComp
Mode
k
196
380kV Busbar
kV
3
P
Q
380kV OHL
general settings as shown in table 17.
level supervision of active power as shown in table 18.
calibration parameters as shown in table 19.
General settings parameters for the Measurement function
Short Description
Disabled / Enabled
Operation
Magnitude factor to scale
power calculations
Angle compensation for phase
shift between measured I & V
Selection of measured current
and voltage
Low pass filter coefficient for
power measurement, V and I
© Copyright 2013 ABB. All rights reserved
IED
ANSI09000039-1-en.vsd
Selected
Comments
value
Enabled
Function must be
1.000
It can be used during commissioning to achieve
higher measurement accuracy. Typically no scaling
is required
0.0
It can be used during commissioning to achieve
higher measurement accuracy. Typically no angle
compensation is required. As well here required
direction of P & Q measurement is towards
protected object (as per IED internal default
direction)
A, B, C
All three phase-to-ground VT inputs are available
0.00
Typically no additional filtering is required
1MRK 505 287-UUS B
PhaseAngleRef using PCM600
Enabled
Busbar protection REB650