ABB Relion 650 Series Applications Manual page 62

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 5
Local human-machine interface
Table 7:
LED state
Off
On
Flashing
5.1.4.2
Parameter management
The LHMI is used to access the IED parameters. Three types of parameters can be read and
written.
Numerical values
String values
Enumerated values
Numerical values are presented either in integer or in decimal format with minimum and maximum
values. Character strings can be edited character by character. Enumerated values have a
predefined set of selectable values.
5.1.4.3
Front communication
The RJ-45 port in the LHMI enables front communication.
The green uplink LED on the left is lit when the cable is successfully connected to the port.
56
Alarm indications
Description
Normal operation. All activation signals are off.
Follow-S sequence: The activation signal is on.
LatchedColl-S sequence: The activation signal is on, or it is off but the indication has not
been acknowledged.
LatchedAck-F-S sequence: The indication has been acknowledged, but the activation signal
is still on.
LatchedAck-S-F sequence: The activation signal is on, or it is off but the indication has not
been acknowledged.
LatchedReset-S sequence: The activation signal is on, or it is off but the indication has not
been acknowledged.
Follow-F sequence: The activation signal is on.
LatchedAck-F-S sequence: The activation signal is on, or it is off but the indication has not
been acknowledged.
LatchedAck-S-F sequence: The indication has been acknowledged, but the activation signal
is still on.
© Copyright 2013 ABB. All rights reserved
1MRK 505 287-UUS B
GUID-5EE466E3-932B-4311-9FE1-76ECD8D6E245 v4
GUID-FD72A445-C8C1-4BFE-90E3-0AC78AE17C45 v8
Busbar protection REB650
Application manual