Section 12
Monitoring
Disturbance report function is characterized by great flexibility as far as configuration, starting
conditions, recording times, and large storage capacity are concerned. Thus, disturbance report is
not dependent on the operation of protective functions, and it can record disturbances that were
not discovered by protective functions for one reason or another. Disturbance report can be used
as an advanced stand-alone disturbance recorder.
Every disturbance report recording is saved in the IED. The same applies to all events, which are
continuously saved in a ring-buffer. Local HMI can be used to get information about the
recordings, and the disturbance report files may be uploaded in the PCM600 using the
Disturbance handling tool, for report reading or further analysis (using WaveWin, that can be
found on the PCM600 installation CD). The user can also upload disturbance report files using FTP
or MMS (over 61850–8–1) clients.
If the IED is connected to a station bus (IEC 61850-8-1), the disturbance recorder (record made and
fault number) and the fault locator information are available as GOOSE or Report Control data.
12.7.3
Setting guidelines
The setting parameters for the Disturbance report function DRPRDRE are set via the local HMI or
PCM600.
It is possible to handle up to 40 analog and 96 binary signals, either internal signals or signals
coming from external inputs. The binary signals are identical in all functions that is, Disturbance
recorder, Event recorder, Indication, Trip value recorder and Sequential of events function.
User-defined names of binary and analog input signals is set using PCM600. The analog and binary
signals appear with their user-defined names. The name is used in all related functions
(Disturbance recorder, Event recorder, Indication, Trip value recorder and Sequential of events ).
Figure
101
blocks. Sequential of events , Event recorder and Indication uses information from the binary input
function blocks (BxRBDR). Trip value recorder uses analog information from the analog input
function blocks (AxRADR),. Disturbance report function acquires information from both AxRADR
and BxRBDR.
200
shows the relations between Disturbance report, included functions and function
© Copyright 2013 ABB. All rights reserved
1MRK 505 287-UUS B
M12179-64 v5
Busbar protection REB650
Application manual