Section 10
Control
989G_OP = 1
989G_CL = 0
If, in this case, line voltage supervision is added, then rather than setting 989 to open state,
specify the state of the voltage supervision:
989_OP = VOLT_OFF
989_CL = VOLT_ON
If there is no voltage supervision, then set the corresponding inputs as follows:
VOLT_OFF = 1
VOLT_ON = 0
10.3.10
Interlocking for line bay ABC_LINE (3)
10.3.10.1
Application
The interlocking for line bay (ABC_LINE, 3) function is used for a line connected to a double busbar
arrangement with a transfer busbar according to figure 88. The function can also be used for a
double busbar arrangement without transfer busbar or a single busbar arrangement with/without
transfer busbar.
189
152
989
ANSI04000478 V1 EN-US
Figure 88: Switchyard layout ABC_LINE (3)
The signals from other bays connected to the module ABC_LINE (3) are described below.
166
WA1 (A)
WA2 (B)
WA7 (C)
289
789
189G
289G
989G
en04000478_ansi.vsd
The interlocking functionality in 650 series can not handle the transfer bus WA7(C).
© Copyright 2013 ABB. All rights reserved
1MRK 505 287-UUS B
IP14139-1 v2
M13561-3 v7
M13560-4 v4
Busbar protection REB650
Application manual