1MRK 505 287-UUS B
10.1.3.3
Single circuit breaker with double busbar, internal voltage selection
Bus 1
Bus 2
Fuse
VT
ANSI10000196 V2 EN-US
Figure 47: Connection of the SESRSYN (25) function block in a single breaker, double busbar
When internal voltage selection is needed, the voltage transformer circuit connections are made
according to figure 47. The voltage from busbar1 VT is connected to V3PB1 and the voltage from
busbar2 VT is connected to V3PB2. The voltage from the line VT is connected to V3PL1. The
positions of the disconnectors and VT fuses shall be connected as shown in figure 47. The voltage
selection parameter
10.1.4
Setting guidelines
The setting parameters for the Synchronizing, synchronism check and energizing check function
SESRSYN (25) are set via the local HMI (LHMI) or PCM600.
This setting guidelines describes the settings of the SESRSYN (25) function via the LHMI.
Common base IED value for primary voltage (
GBASVAL, found under Main menu/Configuration/Power system/Global base values/
X:GBASVAL/VBase. GBASVAL has six instances which can be set independently of each other. The
SESRSYN (25) function has one setting for the bus reference voltage (
setting for the line reference voltage (
set to select one of the six GBASVAL functions used for reference of base values. This means that
the reference voltage of bus and line can be set to different values. The settings for the SESRSYN
(25) function found under Main menu/Settings/Control/SESRCYN(25,SYNC)/X:SESRSYN has
been divided into four different setting groups: General, Synchronizing, Synchrocheck and
Energizing check.
Busbar protection REB650
Application manual
Fuse
VT
189
289
BKR1
52
Fuse
VT
Line
arrangement with internal voltage selection.
CBConfig is set to Double bus .
© Copyright 2013 ABB. All rights reserved
GRP_OFF
SMAI
VBus1
SMAI
VBus2
SMAI
VLine
VBase ) is set in a Global base value function,
GblBaseSelLine ) which independently of each other can be
GUID-1DE55058-62A0-4C9A-9C6A-ACA61B7780D4 v4
SESRSYN (25)
V3PB1*
SYNOK
V3PB2*
AUTOSYOK
V3PL1*
AUTOENOK
V3PL2*
MANSYOK
BLOCK
MANENOK
BLKSYNCH
TSTSYNOK
BLKSC
TSTAUTSY
BLKENERG
TSTMANSY
BUS1_OP
TSTENOK
BUS1_CL
VSELFAIL
BUS2_OP
B1SEL
BUS2_CL
B2SEL
LINE1_OP
L1SEL
LINE1_CL
L2SEL
LINE2_OP
SYNPROGR
LINE2_CL
SYNFAIL
VB1OK
FRDIFSYN
VB1FF
FRDERIVA
VB2OK
VOKSC
VB2FF
VDIFFSC
VL1OK
FRDIFFA
VL1FF
PHDIFFA
VL2OK
FRDIFFM
VL2FF
PHDIFFM
STARTSYN
INADVCLS
TSTSYNCH
VDIFFME
TSTSC
FRDIFFME
TSTENERG
PHDIFFME
AENMODE
Vbus
MENMODE
VLine
MODEAEN
MODEMEN
ANSI10000196-2-en.vsd
GblBaseSelBus ) and one
Section 10
Control
M12330-3 v6
M12329-3 v6