1MRK 505 287-UUS B
11.2
Trip matrix logic TMAGGIO
11.2.1
Identification
Function description
Trip matrix logic
11.2.2
Application
The 12 Trip matrix logic TMAGGIO function each with 32 inputs are used to route trip signals and
other logical output signals to the tripping logics SMPPTRC and SPTPTRC or to different output
contacts on the IED.
TMAGGIO 3 output signals and the physical outputs allows the user to adapt the signals to the
physical tripping outputs according to the specific application needs for settable pulse or steady
output.
11.2.3
Setting guidelines
Operation : Turns the operation of the function Enabled / Disabled .
PulseTime : Defines the pulse time duration. When used for direct tripping of circuit breaker(s) the
pulse time duration shall be set to approximately 0.150 seconds in order to obtain satisfactory
minimum duration of the trip pulse to the circuit breaker trip coils. Used only for
Pulsed .
OnDelay : Used to prevent output signals to be given for spurious inputs. Normally set to 0 or a low
value. Used only for
OffDelay : Defines a minimum on time for the outputs. When used for direct tripping of circuit
breaker(s) the off delay time shall be set to approximately 0.150 seconds in order to obtain a
satisfactory minimum duration of the trip pulse to the circuit breaker trip coils. Used only for
ModeOutputx : Steady .
ModeOutputx : Defines if output signal OUTPUTx (where x=1-3) is Steady or Pulsed . A steady signal
follows the status of the input signals, with respect to
give a pulse once, when the Outputx rises from 0 to 1.
11.3
Configurable logic blocks
11.3.1
Identification
Function description
OR Function block
Busbar protection REB650
Application manual
IEC 61850
identification
TMAGGIO
ModeOutputx : Steady .
IEC 61850
identification
OR
© Copyright 2013 ABB. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
OnDelay and OffDelay . A pulsed signal will
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
Section 11
Logic
SEMOD167882-2 v2
M15321-3 v9
M15291-3 v4
ModeOutputx :
GUID-69C40C61-427D-4EAA-B53D-DB720AFDA13A v1
181