Section 10
Control
289OPTR (22089OTR)(bay 1/sect.B1)
289OPTR (22089OTR)(bay n/sect.B1)
VP289TR (V22089TR)(bay 1/sect.B1)
VP289TR (V22089TR)(bay n/sect.B1)
ANSI04000496 V1 EN-US
Figure 72: Signals from any bays in section B1 to a bus-section disconnector
For a bus-section disconnector, these conditions from the B2 busbar section are valid:
289OPTR (22089OTR)(bay 1/sect.B2)
289OPTR (22089OTR)(bay n/sect.B2)
VP289TR(V22089TR) (bay 1/sect.B2)
VP289TR(V22089TR) (bay n/sect.B2)
EXDU_BB (bay 1/sect.B2)
ANSI04000497 V1 EN-US
Figure 73: Signals from any bays in section B2 to a bus-section disconnector
10.3.6.3
Signals in double-breaker arrangement
If the busbar is divided by bus-section disconnectors, the condition for the busbar disconnector
no other disconnector connected to the bus-section must be made by a project-specific logic.
bay
The same type of module (A1A2_DC) is used for different busbars, that is, for both bus-section
disconnector A1A2_DC and B1B2_DC. But for B1B2_DC, corresponding signals from busbar B are
used.
154
. . .
. . .
. . .
. . .
. . .
. . .
EXDU_BB (bay 1/sect.B1)
. . .
. . .
. . .
EXDU_BB (bay n/sect.B1)
. . .
. . .
. . .
DCOPTR (B2/B3)
. . .
. . .
. . .
VPDCTR (B2/B3)
. . .
. . .
. . .
EXDU_BB (bay n/sect.B2)
EXDU_DC (B2/B3)
© Copyright 2013 ABB. All rights reserved
S1DC_OP
AND
VPS1_DC
AND
EXDU_BB
AND
en04000496_ansi.vsd
S2DC_OP
AND
VPS2_DC
AND
EXDU_BB
AND
en04000497_ansi.vsd
1MRK 505 287-UUS B
M13542-80 v4
Busbar protection REB650
Application manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Reb650

Table of Contents