4.4
Primary Power Port
NOTE: The Primary Power Range is 10VDC to 30VDC.
DC Input / Frame
•
Solid/Stranded Wire: 12-24 awg (2.5-0.2mm).
•
Strip length: 0.28" (7mm).
•
Torque, Terminal Hold-Down Screws: 4.5 – 7 in-lbs (0.50 – 0.78 N-m).
•
DC- is internally connected to I/O V-, but is isolated from CAN V-. A Class 2 power supply must
be used.
POWER UP
1. OPTION: Attach ferrite core with a minimum of two turns of the DC+ and DC- signals from the
DC supply that is powering the controllers.
2. Connect to earth ground.
3. Apply recommended power.
J u l y 6 , 2 0 2 2
MAN1029-10-EN_EXL10_XL10P_UM
P a g e 25 | 195