4.4

Primary Power Port

PIN
-
+
10-30 VDC
supply
Figure 4.3 – Primary Power Port
t h
A p r i l 2 4
, 2 0 2 0
Table 4.1 – Primary Power Port Pins
Signal
0V
+24V
-
+
- +
Figure 4.2 – Power Connector (Primary Power Port)
Solid/Standard Wire: 12-24 awg (2.5-0.2mm).
Strip Length: 0.28" (7 mm)
Torque Rating: 4.5 – 7 in-lbs (0.50 – 0.78 N-m)
DC- is internally connected to I/O, but is isolated from
CAN-V.
A Class 2 power supply must be used
MAN1029-08-EN_EXL10_UserManual
Description
Frame Ground
Input power supply ground
Input power supply positive voltage
Power Connector
Power Up:
Connect to Earth Ground.
Apply 10 – 30VDC.
Screen lights up.
Torque Rating: 4.5 - 7 in-lbs
(0.50 – 0.78 N-m)
DC INPUT / FRAME
.
P a g e 24 | 191