CHAPTER 19:

19.1 Overview

For the EXL10 Series
The Fail-Safe System is a set of features that allow an application to continue running in the event of
certain types of "soft" failures. These "soft" failures include:
Battery power loss
Battery-Backed Register RAM or Application flash corruption due to, for example, an excessive
EMI, Electromagnetic Interference, event.
For the XL10 Prime Series
The Fail-Safe System is a set of features that allow an application to continue running in the event of
certain types of "soft" failures. These "soft" failures include:
Retentive Register or Application flash corruption due to, for example, an excessive EMI,
Electromagnetic Interference, event.
The Fail-Safe System has the following capabilities:
Manually backup the current Retentive Register Settings into flash memory.
Manually restore Register Settings from the values previously backed up in flash memory to
battery-backed RAM.
Detect corrupted Register Settings at power-up and then automatically restore them from flash.
Detect corrupted or empty application in flash memory at power-up and then automatically
load the AUTOLOAD.PGM application file from Removable Media (Compact flash or microSD).
If an automatic Register Restore or Application Load occurs, the OCS can automatically be
placed in RUN mode.
J u l y 6 , 2 0 2 2
FAIL – SAFE SYSTEM
Figure 19.1 – Fail – Safe System Menu
MAN1029-10-EN_EXL10_XL10P_UM
P a g e 163 | 195