8.8

Universal Analog Inputs

NOTE: See the data sheet for the EXL10/XL10 PRIME OCS model being used for jumper settings and see
the appropriate pages in this manual (see Index) for details on how to use Cscape to configure the digital
filtering.
The universal analog inputs provide a high resolution, very flexible interface for a variety of analog inputs.
These inputs include voltage, current, thermocouple, RTD and millivolt. Each channel can be configured
separately using jumpers and configuration settings in Cscape. The HE-EXL1E6 does not require jumpers,
and only requires a configuration parameter in Cscape.
Like the standard analog inputs, these inputs have a digital filter that can be used to filter electrical noise
that may be unavoidable in some installations. The downside to digital filtering is the inputs will respond
more slowly to sudden changes in the actual input.
The Universal Analog Inputs on the Model 6 I/O board are unique from other Horner X-series
input/output cards in that they are configurable through the module configuration instead of having to
change jumper settings in order to setup the input type. To configure the Universal Analog input type:
1) Select Analog In to access the Analog Input Configuration menu.
2) Select any of the Analog input types from the dropdowns by clicking the down arrow beneath
each corresponding Channel, as seen below:
J u l y 6 , 2 0 2 2
Figure 8.8 – Analog Input Configuration Dialog
MAN1029-10-EN_EXL10_XL10P_UM
P a g e 83 | 195