20.4 Modbus Addressing Table for EXL10/XL10 PRIME Units

To access EXL10/XL10 PRIME registers, a Modbus Master must be configured with the appropriate
register type and offset. This is usually accomplished with one of two methods:
Method 1: The first method uses Traditional Modbus References, in which the high digit represents the
register type and the lower digits represent the register offset (starting with Register 1 for each type).
Since only four register types can be represented in this manner, EXL10/XL10 PRIME Modbus Function
Blocks pack several EXL10/XL10 PRIME register types into each Modbus register type. Starting addresses
of each EXL10/XL10 PRIME register type are shown in the Traditional Modbus Reference column of the
Table 20 .1.
Method 2: The second method requires the Modbus Master to be configured with a specific Modbus
Command and Modbus Offset.
EXL10/XL10
Maximum
PRIME
Range
Reference
%I1
2048
%IG1
256
%S1
266
%K1
7
%Q1
2048
%M1
2048
%T1
2048
%QG1
256
%AI1
512
%AIG1
32
%SR1
256
%AQ1
512
%R1
2488
%R1
2048
%AQG1
32
%R1
9999
J u l y 6 , 2 0 2 2
Table 20.1 – Modbus Master Mapping
Trad.
Expanded
Modbus
Modbus Ref.
Ref.
(6 Digits)
(5 Digits)
10001
010001
13001
013001
14001
014001
15001
015001
00001
000001
03001
003001
06001
006001
09001
009001
030001
030001
033001
033001
034001
034001
040001
040001
040513
040513
043001
043001
046001
046001
--
410001
MAN1029-10-EN_EXL10_XL10P_UM
Modbus Commands
Read Input Status (2)
Read Coil Status (1)
Force Coil (5)
Force Multiple Coils (15)
Read Input Register (4)
Read Holding Register (3)
Load Register (6)
Load Multiple Registers (16)
P a g e 173 | 195
Modbus
Offset
0
3000
4000
5000
0
3000
6000
9000
0
3000
4000
0
512
3000
6000
10000