3) Ensure the proper wiring is used for each of the 3 pins A , B, and C on the Universal Analog
Inputs as seen in the reference image below:
Wiring Details:
SPRING CLAMP TERMINALS:
SCREW TERMINALS:
8.9

Analog Outputs

NOTE: Refer to the datasheet for EXL10/XL10 PRIME OCS model being used for details on jumper settings.
The analog outputs on EXL10/XL10 PRIME OCS devices provide high resolution voltage or current outputs.
The voltage or current selection is controlled with jumpers and configuration settings in Cscape.
NOTE: Each channel can be separately configured for voltage or current mode.
When the controller is stopped, the operation of each output is configurable. The outputs can hold the
state they were in before the controller stopped or they can go to a predetermined value. By default,
analog outputs are set to a value of zero. For more information on Stop State, refer to the appropriate
pages (see Index) for the configuration chapter for Cscape settings.
J u l y 6 , 2 0 2 2
Figure 8.9 – Wiring Details
Solid/Stranded wire—16-24 awg (1.5-0.2mm
Strip Length—0.31" (8mm).
Solid/Stranded wire—14-28 awg (2.1-0.08mm
Strip Length—0.24" – 0.28 (6-7mm).
Torque Rating—2 in-lbs (0.2 N-m).
MAN1029-10-EN_EXL10_XL10P_UM