21.8 Backup Battery Replacement

The XL10 has an advanced battery system. It uses a rechargeable lithium battery. The battery powers the
real time clock when power is removed. To store registers, the battery continues to power the OCS for
less than a second after external power is removed. In this time the registers and other retentive data is
saved to internal flash memory. This battery will need eight (8) hours of charging to last approximately
two years when powered off.
NOTE: For the registers to be retentive the battery only needs to be charged and present at power down.
The EXL10/XL10 PRIME OCS uses a lithium-ion battery available from Horner Automation: part no.
BAT00019.
NOTE: Do not use an alkaline AA battery, only the proper battery type listed.
WARNING: DO NOT USE IF BATTERY IS LEAKING OR HAS BEEN DAMAGED.
WARNING: LITHIUM BATTERIES MAY EXPLODE OR CATCH FIRE IF MISTREATED.
DO NOT RECHARGE, DISASSEMBLE, HEAT ABOVE 100° C (212° F) INCINERATE, OR PUNCTURE.
WARNING: EXPLOSION HAZARD – BATTERIES MUST BE ONLY BE CHANGED IN A AREA KNOWN TO BE
NON-HAZARDOUS.
WARNING: Disposal of lithium batteries must be done in accordance with federal, state, and local
regulations. Be sure to consult with the appropriate regulatory agencies before disposing batteries. In
addition, do not recharge, disassemble, heat or incinerate lithium batteries.
WARNING: Do not make substitutions for the battery. Be sure to only use the authorized part number
to replace the battery.