21.7 Battery Status in System Registers

NOTE: Registers NOT supported by the XL Prime controllers.
%SR55.13
%SR195
%SR196
%SR197
%SR198
IMPORTANT: The battery voltage shown in the System Menu and in %SR198 is ONLY valid if the
battery is not in the Charging State. To check battery voltage, power cycle the controller and check
the battery voltage within the first two minutes of power-up. In the first two minutes after power is
applied to the unit, it will be in the 'Waiting' state, which means it is not charging, %SR196 = 11.
J u l y 6 , 2 0 2 2
Table 21.2 – Battery Status
ON if battery is missing or if voltage is below 2.5V
CPU temperature in °C
Charge State; Refer to Table 21.1
Charging Current mA
Battery Voltage in mV