GENERAL CHARACTERISTICS
Phase
Power
Power factor
Battery Bank
Power module
Cabinet
INPUT
Nominal Voltage
Voltage Range
Nominal frequency
Frequency range
Power factor
Harmonic Distortion (THDi)
OUTPUT
Nominal Voltage
Voltage Regulation (Steady state)
Voltage Regulation (Transient)
Nominal frequency
Frequency Range (Synchronized
range)
Overload Capability
Harmonic Distortion (THDv)
Efficaciency
BATTERY / CHARGER
Nominal Voltage
Floating Charge Voltage
Boost Charging Voltage
Temperature Compensation
Maximum Charging Current
MANAGEMENT / COMMUNICATION
Communication
ENVIRONMENT
Operation Temperature
Relative Humidity
Altitude **
IP Class
NORMS
Standard
EMC
LVD
Product specifications are subject to change without further notice.
*When temperature is above 30℃, the output power factor will be de-rated, 0.8 at 31℃~35℃ and 0.7 at 36℃~40℃.
**If the UPS is installed or used in a placewhere the altitude is above than 1000m, the output power must be derated one percent per 100m.
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 04 17 AA 59 201 06
Mod5T
Integrated
305 ~ 478 VAC at 100% load ; 208 ~ 304VAC at <70% load
3 x 380VAC/400VAC/415VAC (3Ph+N) (HV models)
≦± 1% Typical (balanced load) ≦± 2% Typical (unbalanced load)
1 hour for 110%, 10 mins for 120%, 1 min for 150%, 200ms for >150%
≦ 2% THD (Linear Load) ≦ 4% THD (Non-linear Load)
USB & RS232 port (supports Windows 2000/2003/XP/Vista/2008/7/8/10, Linux, Unix and MAC)
Optional SNMP : Power management from SNMP manager (compatible VMware
EN62040-2:2006, EN61000-3-12:2011, EN61000-3-11:2000, EN55024:2010, IEC 61000-4-2:2008, IEC
61000-4-3:2006+A1:2007+A2:2010, IEC61000-4-4:2012, IEC 61000-4-5:2005, IEC 610004-6:2008, IEC
Mod5T
3-Phase in / 3-Phase out
from 30 to 300 kVA
1*
30kVA/30kW
30U / 42U
3 x 380VAC/400VAC/415VAC (3Ph+N)
50/60Hz (Auto sensing)
40Hz ~70Hz
> 0.99 at 100% load, >0.98 at 50% load
< 3% @ 100% load
<=± 5% Typical
50/60Hz
46Hz ~ 54Hz or 56Hz ~ 64Hz
Up to 94.5%
+/- 240V (12V x 40 Pcs)
2.25V/element
2.35V/element
Yes
8A for each power module (ajustable)
and web browser
0 ~ 40°C
0 ~ 95% non-condensing
<1000m for Nominal power
IP 20
CE RoHS
61000-4-8:2009, IEC 61000-2-2:2002
EN 62040 1 : 2008/A1:2013
Mod5T S