Step 5: Then, UPS will enter Battery Mode as shown in the diagram below.
Step 6: Switch ON the output breaker (Q3). Cold start startup procedure is complete.
3.3.3 Maintenance Bypass Operation
Follow the instruction to transfer to Maintenance Bypass and UPS protection as below.
3.3.3.1 Transfer to maintenance bypass
90KVA~210KVA.
Step 1:
Remove the mechanical lock plate of
Maintenance Bypass Breaker.
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line – Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 04 17 AA 59 201 06
300KVA
Remove the mechanical lock plate of
Maintenance Bypass Switch.