Specifications - INFOSEC UPS SYSTEM E6 LCD-RT User Manual

5-6-8-10kva one phase to one phase 10kva three phase to one phase
Table of Contents

Advertisement

Specifications

7.
NPUT
Voltage Range (Vac)
Frequency (Hz)
Number of phases
Input Power factor
THD
OUTPUT
Voltage Range (Vac)
Voltage adjustment
Voltage regulation
Capacity (VA/W)
Power Factor
Output wave form
Frequency stability
Frequency regulation
Transfer time
Crest factor
Efficiency
Nominal autonomy
Cold start
BATTERY
Type
Capacity
Quantity
Voltage (V)
Recharge time
DISPLAY
Status on LCD and LED
Data specified on LCD
Self-diagnostics
PROTECTION
Short circuit
Over heating
Low battery
EPO
Battery
Leakage current
ALARMS
Acoustics & display
PHYSICALS CHARACTERISTICS
Mechanicals dimensions
(wxhxd) mm
Input connectors
Output connectors
Net weight + battery weight
(kgs)
ENVIRONMENT
Operating temp, range
Warning temperature
Altitude
Humidity
Noise
INTERFACE COMPUTER
Type
Slots
compatible systems
COMPLIANCE
Quality
Security
Performance
Standard EMC
Marking
INFOSEC UPS SYSTEM – 4 rue de la Rigotière – 44700 Orvault – France – www.infosec-ups.com
Hot Line Tel : +33 (0)2 40 76 15 82 – fax : +33(0)2 40 94 29 51 – hotline@infosec.fr – 04 09 AA XX 201 19
6
6
E
LCD 5000 RT
E
LCD 6000 RT
200/208/220/230/240 adjustable .(208/120 Vac in option)
Nominal voltage + 1%, + 2%, + 3%, - 1%, - 2%, - 3%
5000
6000
> 5 min
> 8 min
12V / 5 Ah
12 V/ 7 Ah
4 hours at 90%
Normal, Battery, Eco mode, Bypass, Battery low, Default battery, Overload, transfer default and Inverter default
Input voltage, Input frequency, Output voltage, Frequency voltage, charge level, Voltage battery, internal
Mains mode : Bypass Transfer - Battery Mode : Automatic shutdown
Electronic system of management of battery discharge
mains default, Low battery, Overload, environment default
440x176x680
440x88x680
52
24+68
Battery design for use at 25°C. A higher ambient temperature will decrease its life span
Second RS 232, USB, RS 485, relay card, SNMP/ Web card
Windows 95/98/NT/2000/XP/Vista, Novell Netware, Linux etc
6
E
LCD 8000 RT
160-280
45 / 65 Hz
Single phase + ground
> 0,99 (full load)
<6%
± 2%
8000
0,7
Sine wave, THD <3% (from 0 up to 100% in load)
± 0,2% (battery mode)
3 Hz or 1 Hz (program by software)
0 ms
3:1
Up to 90% (normal mode) ; Up to 95% Eco mode
Yes
Lead waterproof and without maintenance
12 V/ 7 Ah
20
240
Temperature
In mains mode, from control panel , by software and
auto test/ 24h
off mode immediately
Alarm and automatic stop
Stop immediate
<3mA in full load
440x132x550
At the bottom to the terminal
At the bottom to the terminal
25+68
0-40°C
0-2000 m up to 40°C / 3000 m up to 35°C
90% max without condensation
< 50dB (at 1 m)
Standard RS 232
ISO 9001 certified manufacturing
EN62040-1-1, IEC 60950-1, UL 1778
EN 62040-3
EN 62040-2, EN61000-3-2, EN61000-3-3, FCC Class A
CE, cUL, UL
6
6
E
LCD 10K RT
E
LCD 10K RT TM
277 - 485
Three phase, R, S, T +
Neutral + Ground
10000
> 5 min
12 V/ 9 Ah
5 hours at 90%
440x132x680
26+68
<30%
10000
28+68
26

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the E6 LCD-RT and is the answer not in the manual?

Questions and answers

Table of Contents