ELECTRO FREEZE Soft Serve Model 99T-RMT
12.1
Compressor/Condensing Circuit Troubleshooting Tables
PROBLEM
Compressor
1.
will not start –
hums
intermittently
2.
(cycling on
overload)
3.
4.
5.
Compressor
1.
starts, but pulls
high amps.
2.
4.
5.
48
PROBABLE CAUSE
Improperly wired.
Low line voltage.
Open start capacitor. (Single phase
only)
High discharge pressure.
Defective compressor
Low line voltage.
Improperly wired.
Running capacitor shorted. (Single
phase only).
Start capacitor weak. (Single phase
only).
REMEDY
1.
Contact your Electro Freeze Distributor
for service.
2.
Ask power company to increase voltage
to not less than 10% below dataplate
rating or have transformer installed.
Have wire checked for inadequate wire
size.
3.
Contact your Electro Freeze Distributor
for service.
4.
See "Discharge pressure too high" this
section.
5.
Contact your Electro Freeze Distributor
for service.
1.
Ask power company to increase voltage
to not less than 10% below nameplate
rating or install transformer.
2.
Contact your Electro Freeze Distributor
for service.
4.
Contact your Electro Freeze Distributor
for service.
5.
Contact your Electro Freeze Distributor
for service.
184621