(G) Control parameters
5.13.8
Output stop function
The motor coasts to a stop (inverter output shutoff) when inverter output frequency falls to Pr. 522
setting or lower.
Pr.
522
G105
● When both of the frequency setting signal and output frequency falls to the frequency set in
Pr. 522 or lower, the inverter stops the output and the motor coasts to a stop.
● At a stop condition, the motor starts running when the frequency setting signal exceeds Pr. 522
+ 2 Hz. The motor is accelerated at the Pr. 13 "Starting frequency" (0.01 Hz under PM motor control)
at the start.
* The output frequency before the slip compensation is compared with the Pr. 522 setting.
Fig. 5-253:
When the output stop function is valid (Pr. 522 ≠ "9999"), the DC injunction brake becomes invalid
NOTE
and the motor coasts to stop when the output frequency drops to the Pr. 522 setting or lower.
5 - 528
Name
Output stop frequency
Example of when target frequency >Pr. 522 + 2 Hz, and start signal is ON/OFF
Output frequency *
Target frequency
(fixed)
Pr. 522+2 Hz
Pr. 522
Pr. 13
STF
RUN
Example for inverter output shutoff
Initial
Setting
value
range
Set the frequency to start coasting to a stop
0 to 590 Hz
(output shutoff ).
9999
9999
No function
Description
Time
Inverter output shutoff
Parameters
I002843E