(E) Environment setting parameters
Writing parameters only during stop (Pr. 77 = "0" initial value)
● Parameters can be written only during a stop in the PU operation mode.
● The following parameters can always be written regardless of the operation mode or operation
status.
Pr.
4 to 6
22
24 to 27
52
54
55
56
72
75
77
79
129
130
133
134
158
160
232 to 239
240
241
268
290
295
296, 297
306
310
340
345, 346
416, 417
434, 435
496, 497
498
550
Tab. 5-27:
Writing during operation is enabled in PU operation mode, but disabled in External operation
mode.
Writing during operation is disabled. To change the parameter setting value, stop the operation.
5 - 70
Name
(Multi-speed setting high-speed,
middle-speed, low-speed)
Stall prevention operation level
(Multi-speed setting speed 4 to speed 7)
Operation panel main monitor selection
FM/CA terminal function selection
Frequency monitoring reference
Current monitoring reference
PWM frequency selection
Reset selection/disconnected PU
detection/PU stop selection
Parameter write selection
Operation mode selection
PID proportional band
PID integral time
PID action set point
PID differential time
AM terminal function selection
User group read selection
(Multi-speed setting speed 8 to speed 15)
Soft-PWM operation selection
Analog input display unit switchover
Monitor decimal digits selection
Monitor negative output selection
Frequency change increment amount
setting
(Password setting)
Analog output signal selection
Analog meter voltage output selection
Communication startup mode selection
(DeviceNet communication)
(PLC function)
(CC-Link communication)
(Remote output)
PLC function flash memory clear
NET mode operation command source
selection
Parameters, that can always be written regardless of the operation mode or operation
status
Pr.
Name
PU mode operation command source
551
selection
555 to 557
(Current average value monitor)
656 to 659
(Analog remote output)
Control circuit temperature signal output
663
level
755 to 758
(Second PID control)
759
PID unit selection
774 to 776
(PU/DU monitor selection)
866
Torque monitoring reference
888, 889
(Free parameter)
891 to 899
(Energy saving monitor)
C0 (900)
FM/CA terminal calibration
C1 (901)
AM terminal calibration
C8 (930)
Current output bias signal
C9 (930)
Current output bias current
C10 (931)
Current output gain signal
C11 (931)
Current output gain current
990
PU buzzer control
991
PU contrast adjustment
Operation panel setting dial push monitor
992
selection
997
Fault initiation
PM parameter initialization
998
Automatic parameter setting
999
1006
Clock (year)
1007
Clock (month, day)
1008
Clock (hour, minute)
Analog meter voltage negative output
1019
selection
1048
Display-off waiting time
1142
Second PID unit selection
1150 to 1199
(PLC function user parameters)
1211 to 1219
(PID gain tuning)
1460 to 1466
(PID multistage set points 1 to 7)
1480 to 1485
(Load characteristics fault detection)
Parameters