Installation and wiring
2.3

Installation of the inverter and enclosure design

When designing or manufacturing an inverter enclosure, determine its structure, size, and device lay-
out by fully considering the conditions such as heat generation of the contained devices and the op-
erating environment. An inverter unit uses many semiconductor devices. To ensure higher reliability
and long period of operation, operate the inverter in the ambient environment that completely sat-
isfies the equipment specifications.
2.3.1

Inverter installation environment

The following table lists the standard specifications of the inverter installation environment. Using
the inverter in an environment that does not satisfy the conditions deteriorates the performance,
shortens the life, and causes a failure. Refer to the following points, and take adequate measures.
Standard environmental specifications of the inverter
Item
Surrounding air
temperature
Ambient humidity
Storage temperature
Atmosphere
Altitude
Vibration
Tab. 2-6:
Temperature applicable for a short time, e.g. in transit.
For the installation at an altitude above 1,000 m up to 2,500 m, derate the rated current 3% per
500 m.
2.9 m/s
Temperature
The permissible surrounding air temperature of the inverter is between –10 °C and +50 °C (–10 °C and
+40 °C at the SLD rating). Always operate the inverter within this temperature range. Operation out-
side this range will considerably shorten the service lives of the semiconductors, parts, capacitors and
others. Take the following measures to keep the surrounding air temperature of the inverter within
the specified range.
● Measures against high temperature
– Use a forced ventilation system or similar cooling system. (Refer to page 2-20.)
– Install the enclosure in an air-conditioned electric chamber.
– Block direct sunlight.
– Provide a shield or similar plate to avoid direct exposure to the radiated heat and wind of a
heat source.
– Ventilate the area around the enclosure well.
FR-F800
LD
SLD
Environmental standard specifications of inverter
2
or less for the FR-F840-04320(185K) or higher.
Installation of the inverter and enclosure design
Description
–10 to +50 °C (non-freezing)
–10 to +40 °C (non-freezing)
With circuit board coating (conforming to IEC60721-3-3 3C2/3S2):
95% RH or less (non-condensing)
Without circuit board coating: 90% RH or less (non-condensing)
-20 to +65 °C
Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Maximum 1,000 m above sea level.
2
5.9 m/s
or less
at 10 to 55 Hz (directions of X, Y, Z axes)
Measurement
position
Inverter
5 cm
5 cm
Measurement
5 cm
position
2 - 17