Mitsubishi Electric FR-F820-04750 Instruction Manual page 251

Hide thumbs Also See for FR-F820-04750:
Table of Contents

Advertisement

Parameters
Decimal
15
14
13
12
11
10
: With warnings, ×: Without warnings
Tab. 5-43:
● The life alarm signal (Y90) turns ON when any of the control circuit capacitor, main circuit capacitor,
cooling fan or inrush current limit circuit reaches the life alarm output level.
● For the terminal used for the Y90 signal, set "90" (positive logic) or "190" (negative logic) in any of
Pr. 190 to Pr. 196 (output terminal function selection).
NOTES
When using an option (FR-A8AY, FR-A8AR, FR-A8NC, FR-A8NCE), the life can be output separately
to the control circuit capacitor life signal (Y86), main circuit capacitor life signal (Y87), cooling fan
life signal (Y88), and inrush current limit circuit life signal (Y89).
Changing the terminal assignment using Pr. 190 to Pr. 196 (output terminal function selection)
may affect the other functions. Set parameters after confirming the function of each terminal.
Life display of the inrush current limit circuit (Pr. 256) (Standard models)
● The life of the inrush current limit circuit (relay, contactor and inrush resistor) is displayed in Pr. 256.
● The number of contact (relay, contactor, thyristor) ON times is counted, and it is counted down
from 100% (0 time) every 1%/10,000 times. As soon as 10% (900,000 times) is reached, Pr. 255 bit
3 is turned ON and also a warning is output to the Y90 signal.
Life display of the control circuit capacitor (Pr. 257)
● The deterioration degree of the control circuit capacitor is displayed in Pr. 257.
● In the operating status, the control circuit capacitor life is calculated from the energization time
and temperature, and is counted down from 100%. As soon as the control circuit capacitor life
falls below 10%, Pr. 255 bit 0 is turned ON and also a warning is output to the Y90 signal.
FR-F800
Pr. 255
Binary
1111
1110
1101
1100
1011
1010
9
1001
8
1000
7
0111
6
0110
5
0101
4
0100
3
0011
2
0010
1
0001
0
0000
Displaying the end of service life by bits
(E) Environment setting parameters
bit3
bit2
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
bit1
bit0
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
5 - 89