Parameters
Pr.
753
A650
754
A652
755
A651
756
A653
757
A654
758
A655
1140
A664
1141
A665
1143
A641
1144
A642
1145
A643
1146
A644
1147
A661
1148
A662
1149
A663
FR-F800
Name
Second PID action
selection
Second PID control
automatic switchover
frequency
Second PID action set
point
Second PID proportional
band
Second PID integral time
Second PID differential
time
Second PID set point/
deviation input selection
Second PID measured
value input selection
Second PID upper limit
Second PID lower limit
Second PID deviation
limit
Second PID signal
operation selection
Second output
interruption detection
time
Second output
interruption detection
level
Second output
1000%
interruption cancel level
Initial
Setting range
Description
value
0, 10, 11, 20, 21,
50, 51, 60, 61, 70,
71, 80, 81, 90, 91,
100, 101, 1000,
0
Refer to Pr. 128.
1001, 1010,
1011, 2000,
2001, 2010,
2011
0 to 600 Hz,
9999
Refer to Pr. 127.
9999
9999
0 to 100%, 9999 Refer to Pr. 133.
0.1 to 1000%,
100
Refer to Pr. 129.
9999
0.1 to 3600 s,
1 s
Refer to Pr. 130.
9999
0.01 to 10 s,
9999
Refer to Pr. 134.
9999
2
1 to 5
Refer to Pr. 609.
3
1 to 5, 101 to 105 Refer to Pr. 610.
9999
0 to 100%, 9999 Refer to Pr. 131.
9999
0 to 100%, 9999 Refer to Pr. 132.
Refer to Pr. 553.
9999
0 to 100%, 9999
(Y205 signal is output.)
0
0 to 3, 10 to 13
Refer to Pr. 554.
1 s
0 to 3600 s, 9999 Refer to Pr. 575.
0 Hz
0 to 600 Hz
Refer to Pr. 576.
900 to 1100%
Refer to Pr. 577.
(A) Application parameters
Set the second PID
control.
For how to enable the
second PID control, refer
to page 5-385.
5 - 349