Multi-Pump Function (Advanced Pid Function) - Mitsubishi Electric FR-F820-04750 Instruction Manual

Hide thumbs Also See for FR-F820-04750:
Table of Contents

Advertisement

(A) Application parameters
5.11.9

Multi-pump function (Advanced PID function)

PID control function can adjust the volume of water, etc. by controlling pumps. When the motor out-
put is insufficient, auxiliary motors can be driven by the commercial power supply. Up to three aux-
iliary motors can be connected.
Pr.
578
A400
579
A401
580
A402
581
A403
582
A404
583
A405
584
A406
585
A407
586
A408
587
A409
588
A410
589
A411
590
A412
591
A413
1370
A442
1376
A414
NOTES
Refer to page 5-347 to set PID control.
When using the SLEEP function, refer to page 5-360 to set the function.
5 - 386
Name
Auxiliary motor operation
selection
Motor connection function
selection
MC switching interlock time
Start waiting time
Auxiliary motor connection-
time deceleration time
Auxiliary motor
disconnection-time
acceleration time
Auxiliary motor 1 starting
frequency
Auxiliary motor 2 starting
frequency
Auxiliary motor 3 starting
frequency
Auxiliary motor 1 stopping
frequency
Auxiliary motor 2 stopping
frequency
Auxiliary motor 3 stopping
frequency
Auxiliary motor start
detection time
Auxiliary motor stop
detection time
Detection time for PID
limiting operation
Auxiliary motor stopping
level
Initial value
Setting
Description
range
FM
CA
0
No auxiliary motor operation
0
1 to 3
Set the number of auxiliary motors to be run.
0
Basic system
1
Alternative system
0
2
Direct system
3
Alternative direct system
1 s
0 to 100 s
Set the MC switchover interlock time.
Set the time from when the MC is switched until it
1 s
0 to 100 s
starts. Set this time a little longer than the MC
switching time.
Used to decrease the output frequency of the
inverter when a motor connection occurs. Set the
0 to 3600 s
deceleration time for decreasing the output
1 s
frequency.
The output frequency is not decreased when a
9999
motor connection occurs.
Used to increase the output frequency of the
inverter when a motor connection occurs. Set the
0 to 3600 s
acceleration time for increasing the output
1 s
frequency.
The output frequency is not increased when a
9999
motor connection occurs.
60 Hz
50 Hz 0 to 590 Hz
60 Hz
50 Hz 0 to 590 Hz
Set the frequency to start the auxiliary motor.
60 Hz
50 Hz 0 to 590 Hz
0 Hz
0 to 590 Hz
0 Hz
0 to 590 Hz
Set the frequency to stop the auxiliary motor.
0 Hz
0 to 590 Hz
Set the delay time until the auxiliary motor is
5 s
0 to 3600 s
started.
Set the delay time until the auxiliary motor is
5 s
0 to 3600 s
stopped.
Set the time until the auxiliary motor is stopped
0 s
0 to 900 s
when the PID overpressure control function is
used.
Set the level for stopping the auxiliary motor by
0 to 100%
the PID overpressure control function.
9999
9999
The PID overpressure control function is disabled.
Parameters