Precautions for use of the inverter
3.1.3

Built-in EMC filter

This inverter is equipped with a built-in EMC filter (capacitive filter) and a common mode choke. Those
filters are effective in reducing air-propagated noise on the input side of the inverter.
To enable the EMC filter, fit the EMC filter ON/OFF connector to the ON position. The FM type is initially
set to "disabled" (OFF), and the CA type to "enabled" (ON).
The input side common mode choke, which is built in the FR-F820-02330(55K) or lower and FR-F840-
01160(55K) or lower inverter, is always enabled regardless of the EMC filter ON/OFF connector setting.
FR-F820-00046(0.75K),
00077(1.5K)
EMC filter OFF
FR-F820-00046(0.75K),
00077(1.5K)
Fig. 3-7:
FR-F800
FR-F820-00105(2.2K) to 00250(5.5K)
FR-F840-00126(5.5K) or lower
EMC filter ON
EMC filter OFF
EMC filter ON
FR-F820-00105(2.2K) to
FR-F820-00340(7.5K) to
00250(5.5K)
00630(15K)
FR-F840-00023(0.75K) to
FR-F840-00170(7.5K) to
00126(5.5K)
00380(18.5K)
Built-in EMC filter
Electro-magnetic interference (EMI) and leakage currents
FR-F820-00340(7.5K) to 00630(15K)
FR-F840-00170(7.5K) to 00380(18.5K)
EMC filter OFF
EMC filter ON
FR-F820-00770(18.5K) to
01250(30K)
FR-F840-00470(22K),
00620(30K)
FR-F820-00770(18.5K) or higher
FR-F840-00470(22K) or higher
EMC filter OFF
EMC filter ON
FR-F820-01540(37K) or higher
FR-F840-00770(37K) or higher
EMC filter
ON/OFF
connector
I002808E